Switch disconnector(1P)
KEY WORDS:High pressure vacuum switch
Classification:
DETAILS
Description:
Outdoor disconnect switch used in 15KV、27KV and 38KV power distribution systems, with current from 200 to 630A. and it used as switching on and switching off at the voltage with no load.
Techincal data:
Maximum voltage (kV) | BIL (kV) | Nominal current (A) | Transient current (kA/Is) | Dimensions | |||
A | B | C | D | ||||
15 | 95 | 200/630 | 16 | 305 | 270 | 580 | 186 |
15 | 95 | 630 | 25 | 305 | 313 | 595 | 230 |
15 | 110 | 200/630 | 16 | 381 | 270 | 650 | 186 |
15 | 110 | 630 | 25 | 381 | 313 | 670 | 230 |
27 | 125 | 200/630 | 16 | 381 | 310 | 650 | 228 |
27 | 125 | 630 | 25 | 381 | 340 | 670 | 260 |
36 | 150 | 630 | 25 | 381 | 368 | 670 | 290 |
36 | 170 | 630 | 25 | 381 | 400 | 670 | 316 |
Related products
Welcome to leave a message for consultation