ZX-32 Recloser
Place of Origin:
China
Price:
Negotiate
Payment Terms:
L/C,D/A,D/P,T/T,Western Union
Specifications
| Rated maximum voltage Ur (kV): | 15.5 | Rated continuous current Ir (A): | 630, 800 |
| Rated lightning impulse withstand voltage Up (kV): | 110 | Power frequency insulation level withstand test voltage Ud (kV): | 50 |
| Rated symmetrical interrupting current Isc (kA): | 12.5, 16 | Rated asymmetrical making current (rms) (kA): | 20, 25 |
| Rated peak making current (kA): | 32.5, 41 | Mechanical life (OPS): | 10,000 |
| Permissible short-circuit operations (OPS): | Up250 | Ambient temperature range (oC): | -40+55 |
| Rated maximum voltage Ur (kV): | 27 | Rated lightning impulse withstand voltage Up (kV): | 125 |
| Power frequency insulation level withstand test voltage Ud (kV): | 60 | Rated symmetrical interrupting current Isc (kA): | 12.5 |
| Rated asymmetrical making current (rms) (kA): | 20 | Rated peak making current (kA): | 32.5 |
| Rated lightning impulse withstand voltage Up (kV): | 150 | Power frequency insulation level withstand test voltage Ud (kV): | 70 |
| Rated maximum voltage Ur (kV): | 38 | Rated lightning impulse withstand voltage Up (kV): | 170 |
Product Description
ZX-Series Distribution Automation Switch The ZX-Series is a three-phase, electronically controlled, vacuum-interrupting distribution automation switch designed for reliable and economical switching, sectionalizing, and advanced metering in circuits rated up to 38 kV. Reliable Performance: Utilizes a ...
ZX-Series Distribution Automation Switch
The ZX-Series is a three-phase, electronically controlled, vacuum-interrupting distribution automation switch designed for reliable and economical switching, sectionalizing, and advanced metering in circuits rated up to 38 kV.
Reliable Performance: Utilizes a magnetic actuator for a lifetime of trouble-free operation.
Advanced Material: Solid cycloaliphatic-epoxy vacuum interrupters; no gaseous, liquid, or foam dielectric.
High Durability: Resistant to ozone, oxygen, moisture, contamination, and ultraviolet light.
Technical Specifications
| Parameter | 15.5 kV | 27 kV (125kV) | 38 kV |
|---|---|---|---|
| Continuous Current (A) | 630, 800 | 630, 800 | 630, 800 |
| Impulse Withstand (kV) | 110 | 125 | 170 |
| Interrupting Current (kA) | 12.5, 16 | 12.5 | 12.5, 16 |
| Mechanical Life (OPS) | 10,000 | 10,000 | 10,000 |
| Temp Range (°C) | -40 to +55 | -40 to +55 | -40 to +55 |
Message for quick reply