Rated maximum voltage Ur (kV): 15.5 Rated continuous current Ir (A): 630, 800
Rated lightning impulse withstand voltage Up (kV): 110 Power frequency insulation level withstand test voltage Ud (kV): 50
Rated symmetrical interrupting current Isc (kA): 12.5, 16 Rated asymmetrical making current (rms) (kA): 20, 25
Rated peak making current (kA): 32.5, 41 Mechanical life (OPS): 10,000
Permissible short-circuit operations (OPS): Up250 Ambient temperature range (oC): -40+55
Rated maximum voltage Ur (kV): 27 Rated lightning impulse withstand voltage Up (kV): 125
Power frequency insulation level withstand test voltage Ud (kV): 60 Rated symmetrical interrupting current Isc (kA): 12.5
Rated asymmetrical making current (rms) (kA): 20 Rated peak making current (kA): 32.5
Rated lightning impulse withstand voltage Up (kV): 150 Power frequency insulation level withstand test voltage Ud (kV): 70
Rated maximum voltage Ur (kV): 38 Rated lightning impulse withstand voltage Up (kV): 170
Product Description
ZX-Series Distribution Automation Switch The ZX-Series is a three-phase, electronically controlled, vacuum-interrupting distribution automation switch designed for reliable and economical switching, sectionalizing, and advanced metering in circuits rated up to 38 kV. Reliable Performance: Utilizes a ...

ZX-Series Distribution Automation Switch

The ZX-Series is a three-phase, electronically controlled, vacuum-interrupting distribution automation switch designed for reliable and economical switching, sectionalizing, and advanced metering in circuits rated up to 38 kV.

Reliable Performance: Utilizes a magnetic actuator for a lifetime of trouble-free operation.
Advanced Material: Solid cycloaliphatic-epoxy vacuum interrupters; no gaseous, liquid, or foam dielectric.
High Durability: Resistant to ozone, oxygen, moisture, contamination, and ultraviolet light.

Technical Specifications

Parameter 15.5 kV 27 kV (125kV) 38 kV
Continuous Current (A)630, 800630, 800630, 800
Impulse Withstand (kV)110125170
Interrupting Current (kA)12.5, 1612.512.5, 16
Mechanical Life (OPS)10,00010,00010,000
Temp Range (°C)-40 to +55-40 to +55-40 to +55