Online Service
Quality Expulsion Fuse Cutout factory
Vacuum Circuit Breaker

SF6 Load Breaker

Specifications
Item: Rated Current Unit: A
12kV: 630 24kV: 630
Item: Rated Voltage Unit: KV
12kV: 12 24kV: 24
Item: 1 Min Power Frequency Withstand Voltage (Dry) 12kV: 42/49
24kV: 50/65 Item: 1 Min Power Frequency Withstand Voltage (Wet)
12kV: 34 24kV: 55
Item: Lightning Impulse Withstand Voltage (Peak) 12kV: 75/85
24kV: 125/145 Item: Rated Frequency
Unit: Hz 12kV: 50
24kV: 63 Item: Rated Short-circuit Closing Current (Peak)
Unit: KA Item: Rated Short-time Withstand Voltage (4s)
12kV: 20 24kV: 25
Item: Rated Peak Withstand Current Item: Rated Operating Voltage (Controller)
Unit: V 12kV: AC220
24kV: AC220 Item: Auxiliary Circuit Rated Voltage
12kV: DC24 24kV: DC24
Item: Mechanical Life Unit: Times
12kV: 3000 24kV: 5000
Item: SF6 Rated Air Pressure (20°C) Unit: MPa
12kV: ≤0.71 24kV: ≤0.71
Item: SF6 Rated Annual Leak Rate Unit: %
12kV: ≤0.5 24kV: ≤0.5
Item: Operation Mode 12kV: Spring Operation (Manual/Electric)
24kV: Spring Operation (Manual/Electric)
Product Description
PLB-12/24 SF6 Load Break Switch The PLB-12/24 SF6 load break switch is a high-reliability, maintenance-free HV electrical equipment designed for 10kV distribution lines. It serves as a vital component for load regulation, control, and distribution automation systems. High reliability and maintenance...

PLB-12/24 SF6 Load Break Switch

The PLB-12/24 SF6 load break switch is a high-reliability, maintenance-free HV electrical equipment designed for 10kV distribution lines. It serves as a vital component for load regulation, control, and distribution automation systems.

  • High reliability and maintenance-free design
  • Available in Manual and Motor-driven configurations
  • Optimized for 10kV distribution network automation
  • Advanced SF6 gas insulation technology
SF6 Load Breaker

Product Attributes

Rated Voltage12kV / 24kV
Rated Frequency50Hz
Operation ModesManual / Motor-driven
MaintenanceMaintenance-free

Technical Specifications

ItemUnit12kV24kV
Rated CurrentA630630
Rated VoltagekV1224
Power Freq. Withstand (Dry)kV42/4950/65
Power Freq. Withstand (Wet)kV3455
Lightning Impulse WithstandkV75/85125/145
Mechanical Lifetimes30005000
SF6 Rated Pressure (20°C)MPa≤0.71≤0.71
Annual Leak Rate%≤0.5≤0.5
Message for quick reply