Online Service
Quality Expulsion Fuse Cutout factory
Vacuum Circuit Breaker

SF6 Load Breaker

Specifications
No.: 1 Item: Rated Voltage
Unit: KV Data: 12/24
No.: 2 Item: Rated Insulation Level (Power Frequency)
Data: Across Open Contacts:49,phase To Phase, Phase To Earth:42 No.: 3
Item: Rated Insulation Level (Wet Withstand Voltage) Data: Phase To Phase, Phase To Earth:34/50
No.: 4 Item: Rated Insulation Level (Impulse Withstand Voltage)
Data: Across Open Contacts:85,phase To Phase, Phase To Earth:75 No.: 5
Item: Rated Power Frequency Unit: Hz
Data: 50/60 No.: 6
Item: Rated Current Unit: A
Data: 630 No.: 7
Item: Rated Active Load Breaking Current Data: 630 (Breaking 100 Times)
No.: 8 Item: Rated Loop Breaking Current
Data: 630 (Breaking 10 Times) No.: 9
Item: 5% Rated Active Load Breaking Current Data: 31.5 (Breaking 20 Times)
No.: 10 Item: Rated Cable Charging Current
Data: 10 (Breaking 20 Times) No.: 11
Item: Rated Short-circuit Making Current(peak) Unit: KA
Data: 50 (Making 5 Times) No.: 12
Item: Rated Short-time Withstand Current(4s) Data: 20
No.: 13 Item: Rated Peak Withstand Current
Data: 50 No.: 14
Item: Rated SF6 Pressure Unit: Mpa
Data: 0.12 No.: 15
Item: Rated SF6 Yearly Gas Leakage Rate Data: ≤1%
Product Description
LW34-12/24 SF6 Load Break Switch The LW34-12/24 SF6 Load Break Switch is engineered for high-performance outdoor 12kV or 24kV three-phase AC 50/60Hz power systems. Designed to reliably open and close load currents and short-circuit currents, this switch ensures stability in demanding electrical ...

LW34-12/24 SF6 Load Break Switch

The LW34-12/24 SF6 Load Break Switch is engineered for high-performance outdoor 12kV or 24kV three-phase AC 50/60Hz power systems. Designed to reliably open and close load currents and short-circuit currents, this switch ensures stability in demanding electrical environments.

Key Advantages

  • Superior Durability: Stainless steel panel offers excellent antisepsis and sealing performance.
  • Maintenance-Free: Engineered for long-term operational reliability without requiring frequent servicing.
  • Safety First: Equipped with an integrated anti-explode device.
  • Operational Efficiency: Lightweight design for easy transit and automatic locking at 0.03 to 0.07MPa pressure.

Product Attributes

Application: Outdoor Power Systems
Material: Stainless Steel Panel
Frequency: 50/60Hz

Technical Specifications

Item Unit Data
Rated voltagekV12/24
Rated currentA630
Rated SF6 pressureMpa0.12
Rated short-time withstand current (4s)kA20
Rated peak withstand currentkA50
Rated SF6 yearly gas leakage rate-≤1%
Message for quick reply